S8FS-C05005D Switch Mode Power Supply ,50W , 5VDC ,Model wtih DIN rail

OmronSKU: S8FS-C05005D
No reviews

Output voltage: S8FS-C05005D
Price:
Sale price0.00 ฿

Shipping calculated at checkout

Stock:
Re-stocking soon

Description

Features

S8FS-C05005D :

  • Power rating : 50 W
  • Output voltage (VDC) : 5 V
  • Input :
  • Efficiency : 115 VAC input (79% typ.) , 230 VAC input (80% typ.)
  • Voltage range :Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.)
  • Frequency : 50 /60 Hz (47 to 450 Hz)
  • Current : 115 VAC input 0.97 A typ. , 230 VAC input 0.59 A typ.
  • Leakage current : 115 VAC input (0.25 mA) , 230 VAC input(0.60 mA)
  • Inrush current (for a cold start at 25°) : 115 VAC input 16 A typ.
    ,230 VAC input 32 A typ.
  • Output :
  • Rated Output Current : 10 A
  • Voltage adjustment range : −10% to 10% (with V. ADJ)
  • Ripple & Noise voltage (100 to 240 VAC input) : 80 mVp-p max.
  • Input variation influence : 0.5% max
  • Load variation influence : 1.0% max.
  • Temperature variation influence (100 to 240 VAC input) : 0.03%/°C max
  • Startup time (115 VAC input) 730 ms typ. , (230 VAC input) 680 ms typ
  • Hold time : (115 VAC input) 12 ms typ. , (230 VAC input) 71 ms typ
    Overvoltage protection : Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

S8FS-C05012D :

  • Power rating : 50 W
  • Output voltage (VDC) : 12 V
  • Input :
  • Efficiency : 115 VAC input (83% typ.) , 230 VAC input (84% typ.)
  • Voltage range :Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on page 18.)
  • Frequency : 50 /60 Hz (47 to 450 Hz)
  • Current : 115 VAC input 0.97 A typ. , 230 VAC input 0.59 A typ.
  • Leakage current : 115 VAC input (0.25 mA) , 230 VAC input (0.55 mA)
  • Inrush current (for a cold start at 25°) : 115 VAC input 16 A typ.
    ,230 VAC input 32 A typ.
  • Output :
  • Rated Output Current : 4.2 A
  • Voltage adjustment range : −10% to 10% (with V. ADJ)
  • Ripple & Noise voltage (100 to 240 VAC input) : 110 mVp-p max.
  • Input variation influence : 0.5% max
  • Load variation influence : 1.0% max.
  • Temperature variation influence (100 to 240 VAC input) : 0.03%/°C max
  • Startup time (115 VAC input) 730 ms typ. , (230 VAC input) 670 ms typ
  • Hold time : (115 VAC input) 14 ms typ. , (230 VAC input) 77 ms typ
    Overvoltage protection : Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

S8FS-C05015D :

  • Power rating : 50 W
  • Output voltage (VDC) : 15 V
  • Input :
  • Efficiency : 115 VAC input (84% typ.) , 230 VAC input (85% typ.)
  • Voltage range :Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on page 18.)
  • Frequency : 50 /60 Hz (47 to 450 Hz)
  • Current : 115 VAC input 0.97 A typ. , 230 VAC input 0.59 A typ.
  • Leakage current : 115 VAC input (0.25 mA) , 230 VAC input (0.55 mA)
  • Inrush current (for a cold start at 25°) : 115 VAC input 16 A typ.
    ,230 VAC input 32 A typ.
  • Output :
  • Rated Output Current : 3.4 A
  • Voltage adjustment range : −10% to 10% (with V. ADJ)
  • Ripple & Noise voltage (100 to 240 VAC input) : 100 mVp-p max.
  • Input variation influence : 0.5% max
  • Load variation influence : 1.0% max.
  • Temperature variation influence (100 to 240 VAC input) : 0.03%/°C max
  • Startup time (115 VAC input) 710 ms typ. , (230 VAC input) 610 ms typ
  • Hold time : (115 VAC input) 14 ms typ. , (230 VAC input) 78 ms typ
    Overvoltage protection : Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

S8FS-C05024D :

  • Power rating : 50 W
  • Output voltage (VDC) : 24 V
  • Input :
  • Efficiency : 115 VAC input (86% typ.) , 230 VAC input (86% typ.)
  • Voltage range :Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on page 18.)
  • Frequency : 50 /60 Hz (47 to 450 Hz)
  • Current : 115 VAC input 0.97 A typ. , 230 VAC input 0.59 A typ.
  • Leakage current : 115 VAC input (0.25 mA) , 230 VAC input (0.55 mA)
  • Inrush current (for a cold start at 25°) : 115 VAC input 16 A typ.
    ,230 VAC input 32 A typ.
  • Output :
  • Rated Output Current : 2.2 A
  • Voltage adjustment range : −10% to 10% (with V. ADJ)
  • Ripple & Noise voltage (100 to 240 VAC input) : 100 mVp-p max.
  • Input variation influence : 0.5% max
  • Load variation influence : 1.0% max.
  • Temperature variation influence (100 to 240 VAC input) : 0.03%/°C max
  • Startup time (115 VAC input) 710 ms typ. , (230 VAC input) 640 ms typ
  • Hold time : (115 VAC input) 14 ms typ. , (230 VAC input) 77 ms typ
    Overvoltage protection : Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

S8FS-C05048D :

  • Power rating : 50 W
  • Output voltage (VDC) : 48 V
  • Input :
  • Efficiency : 115 VAC input (86% typ.) , 230 VAC input (86% typ.)
  • Voltage range :Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on page 18.)
  • Frequency : 50 /60 Hz (47 to 450 Hz)
  • Current : 115 VAC input 0.97 A typ. , 230 VAC input 0.59 A typ.
  • Leakage current : 115 VAC input (0.25 mA) , 230 VAC input (0.55 mA)
  • Inrush current (for a cold start at 25°) : 115 VAC input 16 A typ.
    ,230 VAC input 32 A typ.
  • Output :
  • Rated Output Current : 1.1 A
  • Voltage adjustment range : −10% to 10% (with V. ADJ)
  • Ripple & Noise voltage (100 to 240 VAC input) : 120 mVp-p max.
  • Input variation influence : 0.5% max
  • Load variation influence : 1.0% max.
  • Temperature variation influence (100 to 240 VAC input) : 0.03%/°C max
  • Startup time (115 VAC input) 770 ms typ. , (230 VAC input) 690 ms typ
  • Hold time : (115 VAC input) 14 ms typ. , (230 VAC input) 80 ms typ
    Overvoltage protection : Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

Term and Condition

รับประกันสินค้า : 1 Year

Download

Datasheet
Download

ดูล่าสุด