Description
The S8FS-G series of Switch mode DIN Rail power supplies provide you with excellent standard performance and reliability. They do not require transformers for control circuits plus have in built IEC 61558-2-16 compliant transformers so no need for a transformer with compound windings. The S8FS0G power supplies are excellent with machine tools and semi-conductor equipment plus reduce costs and space. The power supplies include a wealth of features including operating within harsh vibration environments, high temperatures, unstable input voltage and altitudes up to 3000 m.
Features
S8FS-G05005C :
- Power rating : 50 W
- Output voltage : 5 VDC
-
Efficiency :
81 % typ.(at 100 VAC input)
82 % typ.(at 200 VAC input)
82 % typ.(at 230 VAC input) -
Input :
Rated input voltage : 100 to 240 VAC
Allowable input voltage variable range : 85 to 264 VAC(Single-phase), 80 to 370 VDC
Frequency : 50/60Hz (47 to 450 Hz)
Rated input current : 1.1 A typ.(at 100 VAC input), 0.62 A typ.(at 200 VAC input)
Leakage current : 0.5 mA max.(at 100 VAC input) , 1 mA max.(at 200 VAC input)
Inrush current (cold start at 25 ℃) : 14 A typ.(at 100 VAC input), 28 A typ.(at 200 VAC input) -
Output :
Rated output current : 8 A
Output voltage variable range : -10 to +15 % (With V.ADJ)
Ripple : 40 mV(p-p) max.
Static input variation influence : 0.5 % max.
Static load variation influence : 1.0 % max.
Ambient temperature variation influence : 0.05 %/℃ max.
Start up time : 1000 ms max.(at 100 VAC input) , 1000 ms max.(at 200 VAC input)
Hold time : 14 ms typ.(at 100 VAC input) , 75 ms typ.(at 200 VAC input) -
Construction :
Construction : Covered type
Connection : Terminal blocks
Terminal type : Screw terminal
Cooling fan : Cooling fan No
Weight (Main) : 300 g max.
S8FS-G05012C :
- Power rating : 50 W
- Output voltage : 12 VDC
-
Efficiency :
84 % typ.(at 100 VAC input)
86 % typ.(at 200 VAC input)
86 % typ.(at 230 VAC input) -
Input :
Rated input voltage : 100 to 240 VAC
Allowable input voltage variable range : 85 to 264 VAC(Single-phase), 80 to 370 VDC
Frequency : 50/60Hz (47 to 450 Hz)
Rated input current : 1.1 A typ.(at 100 VAC input), 0.62 A typ.(at 200 VAC input)
Leakage current : 0.5 mA max.(at 100 VAC input) , 1 mA max.(at 200 VAC input)
Inrush current (cold start at 25 ℃) : 14 A typ.(at 100 VAC input), 28 A typ.(at 200 VAC input) -
Output :
Rated output current : 4.3 A
Output voltage variable range : -10 to +15 % (With V.ADJ)
Ripple : 40 mV(p-p) max.
Static input variation influence : 0.5 % max.
Static load variation influence : 1.0 % max.
Ambient temperature variation influence : 0.05 %/℃ max.
Start up time : 1000 ms max.(at 100 VAC input) , 1000 ms max.(at 200 VAC input)
Hold time : 11 ms typ.(at 100 VAC input) , 60 ms typ.(at 200 VAC input) -
Construction :
Construction : Covered type
Connection : Terminal blocks
Terminal type : Screw terminal
Cooling fan : Cooling fan No
Weight (Main) : 300 g max.
S8FS-G05015C :
- Power rating : 50 W
- Output voltage : 15 VDC
-
Efficiency :
86 % typ.(at 100 VAC input)
88 % typ.(at 200 VAC input)
88 % typ.(at 230 VAC input) -
Input :
Rated input voltage : 100 to 240 VAC
Allowable input voltage variable range : 85 to 264 VAC(Single-phase), 80 to 370 VDC
Frequency : 50/60Hz (47 to 450 Hz)
Rated input current 1.1 A typ.(at 100 VAC input), 0.62 A typ.(at 200 VAC i: nput)
Leakage current : 0.5 mA max.(at 100 VAC input), 1 mA max.(at 200 VAC input)
Inrush current (cold start at 25 ℃) : 14 A typ.(at 100 VAC input), 28 A typ.(at 200 VAC input) -
Output :
Rated output current : 3.5 A
Output voltage variable range : -10 to +15 % (With V.ADJ)
Ripple : 40 mV(p-p) max.
Static input variation influence : 0.5 % max.
Static load variation influence : 1.0 % max.
Ambient temperature variation influence : 0.05 %/℃ max.
Start up time : 1000 ms max.(at 100 VAC input) , 1000 ms max.(at 200 VAC input)
Hold time : 10 ms typ.(at 100 VAC input) ,60 ms typ.(at 200 VAC input) -
Construction :
Construction : Covered type
Connection : Terminal blocks
Terminal type : Screw terminal
Cooling fan : Cooling fan No
Weight (Main) : 300 g max.
S8FS-G05024C :
- Power rating : 50 W
- Output voltage : 24 VDC
-
Efficiency :
86 % typ.(at 100 VAC input)
89 % typ.(at 200 VAC input)
89 % typ.(at 230 VAC input) -
Input :
Rated input voltage : 100 to 240 VAC
Allowable input voltage variable range : 85 to 264 VAC(Single-phase), 80 to 370 VDC
Frequency : 50/60Hz (47 to 450 Hz)
Rated input current : 1.1 A typ.(at 100 VAC input), 0.62 A typ.(at 200 VAC input)
Leakage current : 0.5 mA max.(at 100 VAC input), 1 mA max.(at 200 VAC input)
Inrush current (cold start at 25 ℃) : 14 A typ.(at 100 VAC input), 28 A typ.(at 200 VAC input) -
Output :
Rated output current : 2.2 A
Output voltage variable range : -10 to +15 % (With V.ADJ)
Ripple : 60 mV(p-p) max.
Static input variation influence : 0.5 % max.
Static load variation influence : 1.0 % max.
Ambient temperature variation influence : 0.05 %/℃ max.
Start up time : 1000 ms max.(at 100 VAC input) , 1000 ms max.(at 200 VAC input)
Hold time : 10 ms typ.(at 100 VAC input) ,55 ms typ.(at 200 VAC input) -
Construction :
Construction : Covered type
Connection : Terminal blocks
Terminal type : Screw terminal
Cooling fan : Cooling fan No
Weight (Main) : 300 g max.
Note : Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.